ระบบเฝ้าระวังและแจ้งเตือนอัตโนมัติ ผ่าน Network, Cellular Network (เครือข่ายโทรศัพท์มือถือ) สำหรับห้อง Data Center, Server Room, Facility Room, Warehouse, ตู้แช่ยา, พื้นที่สำคัญอื่นๆ 081-712-1000 · 090-970-5830 · LINE 063-215-8620

ยี่ห้อ / สินค้าใหม่ 1 ต.ค. 2569

HW group introduces WLD-Location cable L

HWg releases new sensor - WLD-Location cable L

The WLD-Location Cable Type L detects flooding and determines the distance to the point where liquid is detected. When flooding occurs inside buildings or data centers, every second counts. Locating the flooding point makes it possible to quickly identify the exact location, even beneath floors or in inaccessible areas. The WLD-Location cable indicates the location of water, glycol, or other conductive liquid leaks.

The WLD-Location Cable Type L is a sensing cable for detecting water and conductive liquids that also identifies where along the cable the leak occurred. Unlike standard WLD Type A and Type B sensing cables, which only report the presence of liquid somewhere within the entire zone, Type L also locates the position of the leak. Use it where detecting a leak is not enough and its exact location must also be identified. The maximum length of one WLD-L zone is 100 m.

A 5-meter connecting cable is used to connect the location cable to monitoring units equipped with a WLD-L port (green 4-pin connector). The 10 m and 50 m cables simply snap together, with a 4-pin terminator fitted at the end. Unlike Type A and Type B sensing cables, the WLD-Location Cable Type L cannot be extended using a non-sensing extension cable.

Comparison of WLD Location and Sensing Cables

A green 4-pin “WLD-L” port is required to connect the yellow WLD-Location Cable Type L, for example on the Perseus Industrial 310 and Perseus Industrial 315.

Only WLD Type A and Type B sensing cables can be connected to a 2-pin WLD port.

The yellow WLD-Location Cable Type L is connected to the device using the 5 m “WLD-Connecting Cable L 5m.” Distance is measured from zero at this cable connection point.

A special feature of the WLD-L port used to locate flooding is that it can also operate as two independent 2-pin WLD ports after the device configuration is changed.

Locating the liquid along the entire length of the location cable takes 15 to 30 seconds.

Point 0 is the start of the yellow cable (the white 4-pin connector of the 5 m WLD Type L connecting cable).

The flooding point is detected with an accuracy of ±4% (±0.4 m / 10 m).

The yellow WLD Type L cable must be immersed in at least 3 mm of liquid; for fully reliable detection, at least 15 mm of the cable must be in contact with the liquid.

When mechanically installing the yellow WLD Type L cable, observe the minimum bend radius of 25 mm.

WLD cables can be attached to the floor using “WLD-Poro Tape 5m” adhesive tape.